Document Part # 026-4280 Rev 1 Page 31 of 33
©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
AMt 3 Pr2
1:Time with fan at maximum speed
2:Time output ON anti sweat heater
rAL tEr Pr2 Probe for temperature alarm
ALC Ab Pr1 Temperature alarm configuration: relative / absolute
ALU 10 10 10 10 Pr1 High temperature alarm setting
ALL -30 -30 -30 -30 Pr1 Low temperature alarm setting
AHy 1.0 Pr2 Differential for temperature alarm
ALd 15 15 15 15 Pr1 Temperature alarm delay
rA2 nP Pr2 Probe for temperature alarm 2
A2U 150 150 150 150 Pr2 High temperature alarm 2 setting
A2L -40 -40 -40 -40 Pr2 Low temperature alarm 2 setting
A2H 2 Pr2 Differential for temperature alarm 2
A2d 15 15 15 15 Pr2 Temperature alarm delay 2
dAO 1.0 1.0 1.0 1.0 Pr2 Delay of temperature alarm at start-up
EdA 60 Pr2 Alarm delay at the end of defrost
dot 30 Pr2 Temperature alarm exclusion after door open
tbA n Pr2 Silencing alarm relay with buzzer
oA5* ALr Pr2 Relay 5 configuration
oA6* AUS Pr2 Relay 6 configuration
CoM 420 Pr2 Modulating output configuration
AOP CL Pr2 Alarm relay polarity
iAU n Pr2 Auxiliary output independent from ON/OFF state
i1P CL Pr2 Digital input 1 polarity
i1F dor Pr1 Digital input 1 configuration
d1d 15 Pr1 Digital input 1 activation delay
i2P CL Pr2 Digital input 2 polarity
i2F LiG Pr1 Digital input 2 configuration
d2d 5 Pr1 Digital input 2 activation delay
i3P CL Pr2 Digital input 3 polarity
i3F ES Pr1 Digital input 3 configuration
d3d 0 Pr1 Digital input 3 activation delay
nPS 15 Pr1 Pressure switch number
OdC F-C Pr2 Compressor and fan status when open door
rrd 30 Pr2 Outputs restart after door open alarm
CbP y Pr2 Clock presence
Hur --- Pr1 Current hour
Min --- Pr1 Current minutes
dAY --- Pr1 Current day
Hd1 nu Pr1 First weekly day
Hd2 nu Pr1 Second weekly day
Label M1 M2 M3 M4 Menu Parameters Description
Table 17-1 - Default Setting Values