1592023140 XM678D GB r2.8 01.09.2017.docx XM678D 14/15
LABEL VALUE DESCRIPTION RANGE NOTES
CoM
Cur
Modulating output configuration.
PM5; PM6; OA7;
CUr; tEn
For models with PWM / O.C. output:
- PM5 = PWM 50Hz;
- PM6 = PWM 60Hz;
- OA7 = two state, it can be used as an open collector output.
For models with [4 to 20mA] or [0 to 10V] output:
- Cur = 4 to 20mA current output;
- tEn = 0 to 10V voltage output.
AOP
CL
Alarm relay polarity. OP; CL
OP = normally opened.
iAU
n
Auxiliary output independent from
ON/OFF state.
n; Y
if the instrument is switched off also the
switched off;
Y = the auxiliary output state is unrelated to the ON/OFF device
status.
DIGITAL INPUTS
i1P
CL
Digital input 1 polarity. OP; CL
= the digital input is activated by closing the contact;
OP = the digital input is activated by opening the contact.
i1F
dor
Digital input 1 configuration.
EAL; bAL; PAL;
dor; dEF; AUS;
LiG; OnF; Htr;
FHU; ES; HdY
PAL = pressure switch activation; dor = door open;
dEF = defrost activation; AUS = auxiliary activation;
LiG = light activation; OnF = switch on/off the instrument;
Htr = change type of action; FHU = not used;
ES = activate energy saving; HdY = activate holiday function.
d1d
15
Digital input 1 activation delay. 0 to 255min
: time interval to calculate the number of the
pressure switch activation.
When [i1F = EAL or bAL] (external alarms): d1d parameter
defines the time delay between the detection and the successive
signaling of the alarm.
When [i1F = dor]: this is the delay to activate door open alarm.
i2P
CL
Digital input 2 polarity. OP; CL
means the digital input is activated by closing the contact;
OP means the digital input is activated by opening the contact.
i2F
LiG
Digital input 2 configuration.
EAL; bAL; PAL;
dor; dEF; AUS;
LiG; OnF; Htr;
FHU; ES; HdY
PAL = pressure switch activation; dor = door open;
dEF = defrost activation; AUS = auxiliary activation;
LiG = light activation; OnF = switch on/off the instrument;
Htr = change type of action; FHU = not used;
ES = activate energy saving; HdY = activate holiday function.
d2d
5
Digital input 2 activation delay. 0 to 255min
: time interval to calculate the number of the
pressure switch activation.
When [i2F = EAL or bAL] (external alarms): d2d parameter
defines the time delay between the detection and the successive
signaling of the alarm.
When [i2F = dor]: this is the delay to activate door open alarm.
i3P
CL
Digital input 3 polarity. OP; CL
means the digital input is activated by closing the contact;
OP means the digital input is activated by opening the contact.
i3F
ES
Digital input 3 configuration.
EAL; bAL; PAL;
dor; dEF; AUS;
LiG; OnF; Htr;
FHU; ES; HdY
PAL = pressure switch activation; dor = door open;
dEF = defrost activation; AUS = auxiliary activation;
LiG = light activation; OnF = switch on/off the instrument;
Htr = change type of action; FHU = not used;
ES = activate energy saving; HdY = activate holiday function.
d3d
0
Digital input 3 activation delay. 0 to 255min
: time interval to calculate the number of the
pressure switch activation.
When [i3F = EAL or bAL] (external alarms): d3d parameter
defines the time delay between the detection and the successive
signaling of the alarm.
When [i3F = dor]: this is the delay to activate door open alarm.
nPS
15
Number of pressure switch activations
before lock.
0 to 15
Number of activation of the pressure switch, during the
and d3d interval, before signaling the alarm event [i1F, i2F or i3F
= PAL]. If the nPS activation in the d1d, d2d or d3d time is
reached, switch off and on the instrument to restart normal
regulation.
OdC
F-C
Compressor and fan status when open
door.
no; FAn; CPr; F-C
F_C = both Compressor and Fan OFF.
rrd
15
Output restart delay with door open. 0 to 255min
The outputs stopped by the
parameter can restart after
time.
ENERGY SAVING
ESP P1
Energy saving probe selection. nP; P1; P2; P3; P4; P6; tEr
-
HES 0.0
Temperature increasing during Energy
Saving.
[-30.0°C to 30.0°C]
[-54°F to 54°F]
Sets the increasing value of the set point during the Energy Saving
cycle.
PEL nU
Energy saving activation when Light
or/and AUX are switched off.
nU(0); LIG(1); AUS(2); LEA(3)
Energy saving enabled when:
- LiG: light switched off;
- AUS: AUX switched off;
- LEA: both light and AUX switched off.
If nU then not used function.
LAN MANAGEMENT
LMd
y
Defrost Synchronization. n; Y
= the section doesn’t send a global defrost command;
Y = the section sends a command to start defrost to other
controllers.
dEM
y
Defrost end Synchronization. n; Y
the end of the LAN defrosts are i
Y = the end of the LAN defrosts are synchronized.
LSP
n
LAN set-point Synchronization. n; Y
point value is modified only in the local section;
Y = the section set-point, when modified, is updated to the same
value on all the other sections.
LdS
n
LAN Display Synchronization
(temperature sent via LAN).
n; Y
point value is modified only in the local section;
Y = the value displayed by the section is sent to all the other
sections.