Digital Inputs Wiring Diagram and Connections • 13
6.12.Digital Inputs
Terminals [30] through [33] are all free of voltage.
Use a shielded cable for distances higher than one
meter.
For each digital input, configure the parameters:
i1P (polarity of activation), i1F (function of the
input), and i1d (delay of signaling).
The i1P can be set to: cL= active when c
losed; or
oP= active when opened.
The i1F param
eter can be set to: EAL= external
alarm, Bal= serious lock alarm, PAL= pressure
switch alarm, dor= door switch, dEF= external
defrost, AUS= auxiliary activation command,
LiG= light activation, OnF= board On/O
FF,
FHU= do not use this configuration, ES= day/night,
or HdY= do not use this configuration.
The i1d param
eter is for the delay of activation.
For the other digital inputs, sa
me set of parameters is
present: i2P, i2F, i2d, i3P, i3F, i3d.
6.13.Analog Output
Can be set between 4 to 20mA and 0 to 10VDC.
Use a CABCJ15 cable for connections.
The analog output is located near the terminal [39] on
a two-pin connector. The analog output can be used to
control anti-sweat heaters using a chopped phased
controller, XRPW500 (500 watt) or family, XVxxD
or XVxxK.
Figure 6-9 - Digital Inputs
Figure 6-10 - Analog Output