Auxiliary Output Controlling Loads • 35
Probe 4 should be placed on the showcase glass.
For each cabinet, only one probe 4 (P4) can be used;
the P4 will send its value to the other sections that are
connected to the LAN.
Functioning with Probe 4 within the LAN:
Adr n n + 1 n + 2
LCP LCP = n LCP = Y LCP = n
P4C
LAN or probe
not connected
P4C = NTC,
PtC or
PtM
LAN or probe
not connected
trA trA = AC if the device has the analog output
OA6
OA6 = AC if the device will use the AUX relay for
regulation
Functioning Without Probe 4:
In this case, regulation is performed by switching the
auxiliary relay ON and OFF on a 60-minute time
base. The
ON time will be the AMt value, so that the
relay will be ON for AMt minutes and OFF for
[60-AMt] minutes.
In case of P4 error or if P4 is absent, the output is at
AMA value for the AMt
time then the output is at 0
value for the time [255 - AMt] time performing a
simple PWM modulation.
19.6.Auxiliary Output
The auxiliary output is switched ON and OFF by
means of the corresponding digital input or by
pressing and releasing the down arrow key.
Parameter
XM6x8D_1
Without
Probe 4
XM6x8D_2 +
With Probe 4
XM6x8D_3+
Without
Probe 4
Table 19-1 - Functioning with Probe 4 within the LAN
Parameter XM6x8D Without Probe 4
P4C nP
AMt % of ON
Table 19-2 - Functioning Without Probe 4