MODBUS Termination Blocks Default Parameter Map • 49
int 220
Integral time for
room t
emperature
regulation
0 to 255s
This value is used only when
[CrE = Y] or [C
rE = EUP].
It is the
integral time for thermoregulation: high
values mean slower regulation.
0 (zero) = no integral action
CrE Y
Continuous
regulation
activ
ation
n(0); Y(1); EUP(2)
With [C
rE = Y] or [C
rE = EUP], the
regulation becomes PI, HY becomes a
band and int an integral time.
n = stand
ard regulation
Y = continuous regulation, to be used
only in centralized plants
EUP = ev
aporator v
alves
(See Section 19.2., Standard
Regula
tion and Continuous
Regulation)
LS -50 Minimum setpoint
[-67°F to SET]
[-55.0°C to SET]
Sets the minimum acceptable value for
th
e setpoin
t.
US 70 Maximum setpoint
[SET to 302°F]
[SET to 150.0°C]
Sets
the maximum acceptable value for
the setpoin
t.
odS 0
Outputs activation
delay at start up
0 to 255mi
n
This function is enabled at the initial
startup of the devi
ce and inhibits any
output activation for the period of time
set in this parameter (AUX and Light
can work).
AC 0
Anti-short cycle
delay
0
to 60min
Interval between the solenoid valve
stop and the following restart.
CCt 0.0
Continuous cycle
duration
0.0 to 24h00m
in (144)
Compressor ON time during
continuous
cycle: Allows the length of
the continuous cycle to set: compressor
stays ON without interruption for the
CCt time. It can be used, for instance,
when the room is filled with new
products.
Format: hours.1
0m
in
Resolution: 10min
CCS 36
Continuous cycle
setpoint
[-67
°F to 302°F]
[-55.0°C to 150.0°C]
Setpoint for continuous cycle: v
alue
used during the continuous cycle.
Con 15
Compressor ON
time wit
h faulty
probe
0 to 255min
Solenoid valve ON time with faulty
probe: Ti
me du
ring which the solenoid
valve is ON in case of faulty thermostat
probe. With COn = 0, solenoid valve is
always OFF.
CoF 30
Compressor OFF
time wit
h faulty
probe
0 to 255min
Solenoid valve OFF time with faulty
probe: Ti
me du
ring which the solenoid
valve is OFF in case of faulty
thermostat probe. With COF = 0,
solenoid valve is always ON.
Label Value Description Range Notes
Table 24-1 - Default Parameter Map