50 • XM678D I&O Manual 026-1219 Rev 3
CF °F
Temperature
measurement unit
°F(1); °C(0)
°F = Fahrenheit.
°C = Celsius;
CAUTION! When the measurement unit
changes, all para
meters with
temperature values will have to be
checked.
PrU rE Pressure Mode rE(0); Ab(1)
Defines the mode to evaluate the
pressure values
.
CAUTION! Pr
U value is used for all
the
pressure parameters. If [PrU = rE], all
pressure parameters are in relative
pressure unit, if [PrU = Ab], all
pressure parameters are in absolute
pressure unit.
PMU PSI
Pressure
measurement unit
bAr(0); PSI(1); MPA(2)
Selects the pressure measurement units.
MPA means the value of pressure
meas
ured
by kPA*10.
PMd PrE
Pressure probe
visualization
tEM, PrE
Selects the visualization of pressure
probe (P5): tEM
= temperature;
PrE =
pressure
rES dE
Resolution
(only °C)
dE; in
Sets d
ecimal point display.
in =
1°C;
dE = 0.1°C.
Lod tEr
Local display:
default display
nP
(0); P1(1); P2(2);
P
3(3); P
4(4); P5(5);
P6(6); tEr(7); dEF(8)
Selects which probe is displayed by the
in
stru
ment.
nP = no probe;
P1, P2,
P3, P4, P5, P6, tEr = virtu
al
probe for thermostat;
dEF = virtua
l pr
obe for defrost.
rEd tEr
Remote display:
default display
nP
(0); P1(1); P2(2);
P
3(3); P
4(4); P5(5);
P6(6); tEr(7); dEF(8)
It selects which probe is displayed by
th
e X-
REP.
nP = no probe;
P1, P2, P3, P4, P5, P6, tEr
= virtu
al
probe for thermostat;
dEF = virtua
l pr
obe for defrost.
dLY 0.0 Display delay 0.0 to 24h00min (144)
When the temperature changes, the
display
is updated of 1°F/1°C when the
delay time expires.
Format: mi
n.10sec
Resolution: 10sec
rPA P1 Regulation probe A
nP(0); P1(1); P2(2);
P3(3); P4(4);
P6(5)
First probe used to regulate room
temperature. If [
rPA =
nP], the
regulation is performed with the real
value of rPb.
rPb nP Regulation probe B
nP(0); P1(1); P2(2);
P3(3); P4(4);
P6(5)
Second probe used to regulate room
temperature. If [rPb = nP],
the
regulation is perfor
med with the real
value of rPA.
Label Value Description Range Notes
Table 24-1 - Default Parameter Map