MTEC.DXi.H/DXi.HF.GB-3 Use and Maintenance technical manual DXi.H/DXi.HF English
Emibyte DXi.H/DXi.HF Direct expansion close control
2SHUDWLRQOLPLWV
In case of different uses from the overmentioned please contact the Manufacturer.
The unit is designed and built for air conditioning technological environments and must be used exclusively for this
pourpose within its characteristics. All the other uses are not allowed and dissolve the Manufacturer from any liability
for damages caused to the peoples, animals, environment or things.
The minimum temperature of the ambient to be cooled has to be of 18°C.
The maximum temperature of the ambient to be cooled has to be of 35°C.
7KHXQLWVLQVWDQGDUGFRQ¿JXUDWLRQDUHQRWVXLWDEOHIRUPDULQHLQVWDOODWLRQV
Lower heat load will not ensure precise temperature and humidity control than causing frequent compressor start
& stop.
7KHURRPKHDWORDGFDQQRWEHOHVVWKDQRIWKHVHQVLEOHFRROLQJFDSDFLW\RIWKHSUHFLVLRQDLUFRQGLWLRQHU
Indoor air conditions
Temperature From 20°C to 35°C
Relative humidity )URPWR
Hot water circuit
Water inlet temperature Max. 85°C
Water pressure Max. 8.5 bar
Storage conditions
Temperature From -20°C to 50°C
6SHFL¿FKXPLGLW\
Maximum relative humidity percen-
WDJHDFFHSWHGLVWRSUHYHQW
condensation on surfaces
Power supply tolerances 9+]
2SHUDWLRQOLPLWV