Emotron VSB Instruction Manual Chapter 6 Specification of Parameters
Tak e keypad potentiometer for example, automatic correction is as follows
1) Set C4-00 to 2 in stop status and press ENT key to confirm. In this way, keypad
potentiometer is selected as correction channel.
2) Input a relatively low analog voltage (e.g. about 1V) via potentiometer, and input the
theoretical value of this analog voltage by C4-06 after the stabilization of this voltage
input, and then press ENT key to confirm.
3) Input a relatively high analog voltage (e.g. about 5V) via potentiometer, and input the
theoretical value of this analog voltage by C4-08 after the stabilization of this voltage
input, and then press ENT key to confirm.
4) Upon the successful correction, C4-00 parameter will be restored to zero.
ATTENTION:
Set the theoretical value or actual value of analog voltage in C4-06 and C4-08. This
value can be either the set value of analog output of peripheral equipment, or the actual
voltage value of analog input measured by a multimeter or other instruments.
C4-05 and C4-07 are the sampling values of analog input voltage. These values is for
reference only. Do not write the value of C4-05 directly into C4-06, or write the value of
C4-07 directly into C4-08.
- 110 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emotron VSB Series and is the answer not in the manual?

Emotron VSB Series Specifications

General IconGeneral
BrandEmotron
ModelVSB Series
CategoryController
LanguageEnglish

Related product manuals