Step 8 (continued): A note
about multi-pole breakers
If 2- or 3-pole breakers are to be monitored,
we recommended that one CT be used for on
each pole; however, to conserve the number
of CTs, a single CT can be used. To use a
single CT, clasp the clamp around either one
of the non-neutral leads coming off the
breaker (it doesn’t matter which). When only
one CT is used, input a circuit multiplier in the
app to double or triple the reading by entering
a “2” or “1.7”. Using a single CT to monitor a
multi-pole breaker does not accurately
monitor unbalanced loads.
Need help?
emporiaenergy.com/support
support@emporiaenergy.com
1-844-EMPORIA (367-6742)
Most accurate - Attach one
branch sensor on each leg of
the breaker
Less accurate - Attach one
branch sensor on a single leg
and use an app multiplier.