Wiring Cerabar M HART
18 Endress+Hauser
4 Wiring
4.1 Connecting the device
!
Note!
When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings.
Protective circuits to prevent reverse polarity, HF influences and overvoltage peaks are installed.
The shield or grounding (if present) must always be connected to the internal ground terminal
p
in the housing.
The supply voltage must match the power supply on the nameplate (see Page 6, Section 2.1.1
"Nameplates").
Switch off the supply voltage before connecting the device.
Unscrew the housing cover.
If present, remove the retaining ring with the onsite display.
Push up the latch with the arrow until the grip of the retaining ring is audibly released.
Release the retaining ring carefully to prevent damage to the display cables. The connector of
the display can remain plugged in.
Guide the cable through the gland. Preferably use twisted, shielded two-wire cable.
Connect the device in accordance with the following diagram.
Where applicable, refit the retaining ring with the onsite display. The grip of the retaining ring
clips in with an audible click.
Screw down housing cover.
Switch on supply voltage.
P01-PMx4xxxx-04-xx-xx-xx-013
Fig. 17: Electrical connection 4 to 20 mA
Disassembling the onsite display: To release the retaining ring from the electronic insert, push up the latch with
the arrow.
The terminal n on the electronic insert is for grounding and is already wired internally. If the connecting cable
also has a shielding or ground cable within it, then this may only be connected to the internal ground terminal
p
of the housing, not to terminal
n. The terminals are designed to take one wire each.
4 to 20 mA test signal: you can take a 4 to 20 mA test signal via the terminal lugs without interrupting the
measurement.
1
2
3
+
3
4
+
+
Zero
Damping
on off
Span
Display