Cerabar S PMP71 with 4 to 20 mA HART Operation
Endress+Hauser 33
5.9 Factory setting (reset)
By entering a certain code, you can completely, or partially, reset the entries for the parameters to
the factory settings. ( For factory settings, refer to Operating Instructions BA00413P "Description of
device functions"). Enter the code by means of the ENTER RESET CODE parameter (menu path:
(GROUP SELECTION ) OPERATING MENU OPERATION).
There are various reset codes for the device. The following table illustrates which parameters are
reset by the particular reset codes. Operation must be unlocked to reset parameters ( ä 31,
"Locking/unlocking operation").
!
Note!
Any customer-specific configuration carried out by the factory is not affected by a reset (customer-
specific configuration remains). If you want to change the customer-specific configuration set at the
factory, please contact Endress+Hauser Service.
Reset code Description and effect
1846 Display reset
This reset resets all the parameters which have to do with how the display appears
(DISPLAY group).
Any simulation which may be running is ended.
The device is restarted.
62 PowerUp reset (warm start)
This reset resets all the parameters in the RAM. Data are read back anew from the
EEPROM (processor is reinitialized).
Any simulation which may be running is ended.
The device is restarted.
333 User reset
This reset resets the following parameters:
Function group POSITION ADJUSTMENT
Function group BASIC SETUP, except for the customer-specific units
Function group EXTENDED SETUP
–Group OUTPUT
Function group HART DATA: BUS ADDRESS and PREAMBLE NUMBER
Any simulation which may be running is ended.
The device is restarted.
7864 Total reset
This reset resets the following parameters:
Function group POSITION ADJUSTMENT
Function group BASIC SETUP
Function group EXTENDED SETUP
Function group LINEARIZATION (an existing linearization table is erased)
–Group OUTPUT
Function group HART DATA
Function group MESSAGES
All configurable messages ("Error" type) are reset to the factory setting.
ä 39, "Messages" and ä 46, "Response of outputs to errors".
Function group USER LIMITS
Function group SYSTEM 2
Any simulation which may be running is ended.
The device is restarted.
8888 HistoROM reset
The measured value memory and event memory are cleared. During the reset, the
HistoROM must be attached to the electronic insert.