Cerabar S PMP71 with 4 to 20 mA HART Commissioning
Endress+Hauser 37
!
Note!
For onsite operation, see also:
→ ä 23, "Function of the operating elements – onsite display connected" and
→ ä 25, "Onsite operation – onsite display connected".
6.5 Lead sealing plan
Lead sealing of the housing cover is provided for use in applications subject to custody transfer
regulations:
P01-MIDxxxxx-19-xx-xx-xx-031
SET LRV
Set the measuring range (enter 4 mA value).
Specify a pressure value for the lower current value
(4 mA value). A reference pressure does not have to be
present at the device.
SET LRV
Set the measuring range (enter 4 mA value).
Specify a pressure value for the lower current value
(4 mA value). A reference pressure does not have to be
present at the device.
SET URV
Set the measuring range (enter 20 mA value).
Specify a pressure value for the upper current value
(20 mA value). A reference pressure does not have to be
present at the device.
SET URV
Set the measuring range (enter 20 mA value).
Specify a pressure value for the upper current value
(20 mA value). A reference pressure does not have to be
present at the device.
DAMPING TIME
Enter damping time (time constant τ). The damping
affects the speed at which all subsequent elements, such
as the onsite display, measured value and current output
react to a change in the pressure.
DAMPING TIME
Enter damping time (time constant τ). The damping
affects the speed at which all subsequent elements, such
as the onsite display, measured value and current output
react to a change in the pressure.
Onsite operation Digital communication
FIELD TERMINALSFIELD TERMINALS