Cerabar S PMP71 with 4 to 20 mA HART Troubleshooting
Endress+Hauser 39
8 Troubleshooting
8.1 Messages
The following table lists all the possible messages that can occur.
The device makes a distinction between the error types "Alarm", "Warning" and "Error". You may
specify whether the device should react as if for an "Alarm" or "Warning" for "Error" messages. See
"Message type/NA 64" column and ä 46, "Response of outputs to errors".
In addition, the "Error type/NA 64" column classifies the messages in accordance with NAMUR
Recommendation NA 64:
Break down: indicated with "B"
Maintenance need: indicated with "C" (check request)
Function check: indicated with "I" (in service)
Error message display on the onsite display:
The measured value display shows the message with the highest priority. See the "Priority"
column.
The ALARM STATUS parameter shows all the messages present in descending order of priority.
You can scroll through all the messages present with the S key or O key.
Message display via digital communication:
The ALARM STATUS parameter shows the message with the highest priority.
See the "Priority" column.
!
Note!
If the device detects a defect in the onsite display during initialization, special error messages are
generated. For error messages, see ä 45, "Onsite display error messages".
For support and further information, please contact Endress+Hauser Service.
See also "Repair", "Repair of Ex-certified devices" and "Spare Parts".
Code Error type/
NA 64
Message/description Cause Measure Priority
101 (A101) Alarm
B
B>Sensor electronic EEPROM
error
Electromagnetic effects are greater
than specifications in the technical
data.
( ä 51) This message normally
only appears briefly.
Wait a few minutes.
Restart the device. Perform reset
(Code 62).
Block off electromagnetic effects or
eliminate source of disturbance.
17
Sensor defective. Replace sensor.
102 (W102) Warning
C
C>Checksum error in EEPROM:
peakhold segment
Main electronics defective. Correct
measurement can continue as long
as you do not need the peak hold
indicator function.
Replace main electronics. 53
106 (W106) Warning
C
C>Downloading - please wait Downloading. Wait for download to complete. 52
110 (A110) Alarm
B
B>Checksum error in EEPROM:
configuration segment
The supply voltage is disconnected
when writing.
Reestablish supply voltage. Perform
reset (Code 7864) if necessary.
Carry out calibration again.
6
Electromagnetic effects are greater
than specifications in the technical
data. ( ä 51)
Block off electromagnetic effects or
eliminate sources of disturbance.
Main electronics defective. Replace main electronics.
113 (A113) Alarm
B
B>ROM failure in transmitter
electronic
Main electronics defective. Replace main electronics. 1
115 (E115) Error
B
Factory
setting:
Warning
B>Sensor overpressure Overpressure present. Reduce pressure until message
disappears.
29
Sensor defective. Replace sensor.