Troubleshooting Cerabar S PMP71 with 4 to 20 mA HART
40 Endress+Hauser
116 (W116) Warning
C
C>Download error, repeat
download
The file is defective. Use another file. 36
During the download, the data are
not correctly transmitted to the
processor, e.g. because of open cable
connections, spikes (ripple) on the
supply voltage or electromagnetic
effects.
Check cable connection PC
transmitter.
Block off electromagnetic effects or
eliminate sources of disturbance.
Perform reset (Code 7864) and carry
out calibration again.
Repeat download.
120 (E120) Error
B
Factory
setting:
Warning
B>Sensor low pressure Pressure too low. Increase pressure until message
disappears.
30
–Sensor defective. –Replace sensor.
121 (A121) Alarm
B
B>Checksum error in factory
segment of EEPROM
Main electronics defective. Replace main electronics. 5
122 (A122) Alarm
B
B>Sensor not connected Cable connection sensor –main
electronics disconnected.
Check cable connection and repair if
necessary.
13
Electromagnetic effects are greater
than specifications in the technical
data. ( ä 51)
Block off electromagnetic effects or
eliminate source of disturbance.
Main electronics defective. Replace main electronics.
–Sensor defective. –Replace sensor.
130 (A130) Alarm
B
B>EEPROM is defective. Main electronics defective. Replace main electronics. 10
131 (A131) Alarm
B
B>Checksum error in EEPROM:
min/max segment
Main electronics defective. Replace main electronics. 9
132 (A132) Alarm
B
B>Checksum error in totalizer
EEPROM
Main electronics defective. Replace main electronics. 7
133 (A133) Alarm
B
B>Checksum error in History
EEPROM
An error occurred when writing. Perform reset (Code 7864) and carry
out calibration again.
8
Main electronics defective. Replace main electronics.
602 (W602) Warning
C
C>Linearization curve not
monotone
The linearization table is not
monotonic increasing or decreasing.
Add to or correct linearization table.
Then accept linearization table
again.
57
604 (W604) Warning
C
C>Linearization table not valid.
Less than 2 points or points too
close
The linearization table consists of
less than 2 points.
Add to linearization table. If
necessary, confirm linearization
table again.
58
At least 2 points in the linearization
table are too close together. A
minimum gap of 0.5 % of the span
must be maintained between two
points.
Spans for the "Pressure linearized"
option: HYDR. PRESS MAX. –
HYDR. PRESS MIN.; TANK
CONTENT MAX. – TANK
CONTENT MIN.
Spans for the "Height linearized"
option: LEVEL MAX. – LEVEL
MIN.; TANK CONTENT MAX. –
TANK CONTENT MIN.
Correct linearization table and
accept again.
613 (W613) Warning
I
I>Simulation is active Simulation is switched on, i.e. the
device is not measuring at present.
Switch off simulation. 60
Code Error type/
NA 64
Message/description Cause Measure Priority