Troubleshooting Cerabar S PMP71 with 4 to 20 mA HART
42 Endress+Hauser
710 (W710) Warning
C
B>Set span too small. Not
allowed.
Values for calibration (e.g. lower-
range value and upper-range value)
are too close together.
Adjust calibration to suit sensor. (See
also Operating Instructions
BA00413P, parameter description
MINIMUM SPAN or these
Operating Instructions)
51
The sensor was replaced and the
customer-specific configuration does
not suit the sensor.
Adjust calibration to suit sensor.
Replace sensor with a suitable
sensor.
Unsuitable download carried out. Check configuration and perform
download again.
711 (A711) Alarm
B
B>LRV or URV out of edit limits Lower-range value and/or upper-
range value undershoot or overshoot
the sensor range limits.
Reconfigure lower-range value and/
or upper-range value to suit the
sensor. Pay attention to position
factor.
37
The sensor was replaced and the
customer-specific configuration does
not suit the sensor.
Reconfigure lower-range value and/
or upper-range value to suit the
sensor. Pay attention to position
factor.
Replace sensor with a suitable
sensor.
Unsuitable download carried out. Check configuration and perform
download again.
713 (A713) Alarm
B
B>100% POINT level out of edit
limits
The sensor was replaced. Carry out calibration again. 39
715 (E715) Error
C
Factory
setting:
Warning
C>Sensor over temperature The temperature measured in the
sensor is greater than the upper
nominal temperature of the sensor.
(See also Operating Instructions
BA00413P, parameter description
Tmax SENSOR or these Operating
Instructions)
Reduce process temperature/
ambient temperature.
32
Unsuitable download carried out. Check configuration and perform
download again.
716 (E716) Error
B
Factory
setting:
Alarm
B>Process isolating diaphragm
broken
–Sensor defective. –Replace sensor.
Reduce pressure.
24
717 (E717) Error
C
Factory
setting:
Warning
C>Transmitter over temperature The temperature measured in the
electronics is greater than the upper
nominal temperature of the
electronics (+88 °C (+190 °F)).
Reduce ambient temperature. 34
Unsuitable download carried out. Check configuration and perform
download again.
718 (E718) Error
C
Factory
setting:
Warning
C>Transmitter under temperature The temperature measured in the
electronics is less than the lower
nominal temperature of the
electronics
(–43 °C (-45 °F)).
Increase ambient temperature.
Insulate device if necessary.
35
Unsuitable download carried out. Check configuration and perform
download again.
719 (A719) Alarm
B
B>Y-VAL of lin. table out of edit
limits
At least one Y-VALUE in the
linearization table is below the MIN.
TANK CONTENT or above the
MAX. TANK CONTENT.
Carry out calibration again. (See also
Operating Instructions BA00413P,
Section 5 or these Operating
Instructions)
40
Code Error type/
NA 64
Message/description Cause Measure Priority