Cerabar S PMP71 with 4 to 20 mA HART Troubleshooting
Endress+Hauser 43
720 (E720) Error
C
Factory
setting:
Warning
C>Sensor under temperature The temperature measured in the
sensor is smaller than the lower
nominal temperature of the sensor.
(See also Operating Instructions
BA00413P, parameter description
Tmin SENSOR or these Operating
Instructions)
Increase process temperature/
ambient temperature.
33
Unsuitable download carried out. Check configuration and perform
download again.
Loose connection at sensor cable Wait a short period of time and
tighten the connection, or avoid
loose connection.
721 (A721) Alarm
B
B>ZERO POSITION level out of
edit limits
LEVEL MIN or LEVEL MAX has
been changed.
Perform reset (Code 2710) and carry
out calibration again.
41
722 (A722) Alarm
B
B>EMPTY CALIB. or FULL
CALIB. out of edit limits
LEVEL MIN or LEVEL MAX has
been changed.
Perform reset (Code 2710) and carry
out calibration again.
42
723 (A723) Alarm
B
B>MAX. FLOW out of edit limits FLOW-MEAS. TYPE has been
changed.
Carry out calibration again. 43
725 (A725) Alarm
B
B>Sensor connection error, cycle
disturbance
Electromagnetic effects are greater
than specifications in the technical
data. (See Kap. 9.)
Setscrew loose.
Block off electromagnetic effects or
eliminate source of disturbance.
Tighten setscrew with a torque of 1
Nm (0.74 lbf ft) (see Kap. 3.3.4).
25
Sensor or main electronics defective. Replace sensor or main electronics.
726 (E726) Error
C
Factory
setting:
Warning
C>Sensor temperature error -
overrange
Electromagnetic effects are greater
than specifications in the technical
data. ( ä 51)
Block off electromagnetic effects or
eliminate source of disturbance.
31
Process temperature is outside
permitted range.
Check temperature present, reduce
or increase if necessary.
Sensor defective. If the process temperature is within
the permitted range, replace sensor.
727 (E727) Error
C
Factory
setting:
Warning
C>Sensor pressure error -
overrange
Electromagnetic effects are greater
than specifications in the technical
data. ( ä 51)
Block off electromagnetic effects or
eliminate source of disturbance.
28
Pressure is outside permitted range. Check pressure present, reduce or
increase if necessary.
Sensor defective. If the pressure is within the
permitted range, replace sensor.
728 (A728) Alarm
B
B>RAM error Fault in the main electronics. Briefly disconnect device from the
power supply.
2
Main electronics defective. Replace main electronics.
729 (A729) Alarm
B
B>RAM error Fault in the main electronics. Briefly disconnect device from the
power supply.
3
Main electronics defective. Replace main electronics.
Code Error type/
NA 64
Message/description Cause Measure Priority