2.2 Mounting instructions with diaphragm seal
Cerabar S
with diaphragm seal
– PMC 635
– PMP 635
The Cerabar S with diaphragm seal is
screwed in, flanged or clamped,
depending on the type of diaphragm seal.
The protective cap of the diaphragm
seal should only be removed just before
mounting in order to protect the
diaphragm.
The diaphragm of the diaphragm seal of
the Cerabar S must not be pressed in or
cleaned with pointed or hard objects.
The diaphragm seal and the pressure
sensor together form a closed and
calibrated system which is filled with
filling fluid through a hole in the upper
part. The following rules should be
observed:
This hole is sealed and not to be
opened.
The instrument should only be turned
by the diaphragm seal and not by the
housing.
Level measurementFor level measurement the Cerabar S must
always be installed below the lowest
measuring point.
The instrument should not be installed
within the flow of material, in the outlet
of the tank or at a place in the tank
where pressure pulses from agitator
blades may occur.
Calibration and function testing are
easier to carry out if the Cerabar S is
mounted downstream from a shut-off
valve.
Mounting with
temperature spacers
The use of temperature spacers is
recommended when the continuous
extreme product temperatures cause the
maximum permissible ambient
temperature to exceed +85 °C.
Note when mounting that the
temperature spacer increases the
maximum height by 100 mm.
Due to the hydrostatic column in the
temperature spacer, the increased
height also causes a zero point shift of
approx. 10 mbar.
0 - 10 bar
BA211Y13
Figure 2.6
When screwing in the Cerabar S
with diaphragm seals, turn by the
diaphragm seal only, not by the
housing.
0 - 10 bar
BA211Y14
0 - 10 bar
A + 100
100
BA211Y15
Figure 2.7
Temperature spacer
Cerabar S FF 2 Installation
Endress+Hauser 11