Mounting with capillary
tubing
To protect from high temperatures, moisture or vibration, or where the mounting point is
not easily accessible, the housing of the Cerabar S can be mounted with capillary tubing
away from the measuring point.
A bracket for mounting on a wall or pipe is available for this.
2.3 Mounting accessories
Wall and pipe mounting
with accessories
0 - 10 bar
Mounting point away from
the measuring point
Measuring point:
• very moist
• hot
• strongly vibrating
• difficult to access
BA211Y16
0 - 10 bar
Ø 60.3
90
87
73
Ø 6
BA211Y17
183
81
A*
118
70
111
/ 60,3
0 - 10 bar
PMC 731 A = 19 mm
PMP 731
Flush-mounted diaphragm
A = 18 mm
PMP 731
Internal diaphragm
A = 44 mm
BA211Y18
Figure 2.8
left:
•
Mounted with bracket on
horizontal piping
right:
•
Mounted with bracket on a wall
118
B*
3
94
166
0 - 10 bar
BA211Y19
ø60,3
90
ø6
73
87
0 - 10 bar
BA211Y20
Figure 2.9
•
Mounted with bracket on
vertical piping
PMC 731 B = 19 mm
PMP 731
Flush-mounted diaphragm
B = 18 mm
PMP 731
Internal diaphragm
B = 44 mm
2 Installation Cerabar S FF
12 Endress+Hauser