Bias pressure
If the display (when present) does not display zero after calibration when the process
pressure p
e
= 0, then it can be corrected to zero by registering the bias pressure.
# Key Entry
1 Correct display:
Press +Z and +S twice
simultaneously: An acting bias
pressure is registered
2 Display bias pressure:
Press +Z and +S once
simultaneously: An entered bias
pressure is briefly displayed
3 Delete bias pressure:
Press -Z and -S twice simultaneously:
An entered bias pressure is deleted
5.2 Calibration via a configuration tool
The calibration is made via a configuration tool (remote operation).
–
–
+
Z
S
+
–
–
+
Z
S
+
–
–
+
+
Z
S
Parameter Description
Lower Range
Value
Entry of lower range-value – zero (bargraph)
Upper Range
Value
Entry of upper range-value – span; max. turndown 20:1 (bargraph)
Set Lower Range
Value
Acting reference pressure is taken as lower range-value (bargraph)
Set Upper Range
Value
Acting reference pressure is taken as upper range-value; max. turndown 20:1
(bargraph)
Set Bias Pressure
Entry bias pressure (only affects display module)
Bias Pres Autom
Acting pressure is taken as bias pressure (only affects display module)
Set Output Damp.
Entry of damping τ (0...40 s)
Select Press Unit
Options pressure unit: mbar, bar, Pa, hPa, kPa, MPa, mm H
2
O, m H
2
O, in H
2
O,
ft H
2
O, psi, g / cm
2
, kg / cm
2
, kgf / cm
2
, atm, lb / ft
2
, torr, mm Hg or in Hg.
Linearization
Operating mode: linear (pressure)
0...2 bar g
p
p
Bias
p+p
Bias
p
e
=0
BA211Y35
pipe full
Cerabar S FF 5 Pressure Measurement
Endress+Hauser 33