6.2 Empty/full calibration
The empty/full calibration lays down the desired minimum and maximum levels for
measurement. The entries can be made in any units. There are two prerequisites:
• The Cerabar S has been mounted.
• The tank can be filled.
"Level linear"
# Parameter Entry Significance
1 Default
Values
5140 Reset to factory
setting
2 Linerazition "level
linear"
Operating mode
3 The tank is empty (0...40 %)
4 Set Lower
Value
Confirm Register pressure
5 Start Point e.g. 0 Current level =
level for "empty"
6 The tank is full (60...100 %)
7 Set Upper
Value
Confirm Register pressure
8 Full Scale e.g. 100 Current level =
level for "full"
9 Unit After Lin e.g. % Select level units
Result
• Level is displayed in "Measured Value"
"Level horizontal
cylinder"
# Parameter Entry Significance
1 Default Value 5140 Reset to factory
setting
2 Linearization "level
horizontal
cylinder"
Operating mode
3 The tank is empty (0...40 %)
4 Set Lower
Value
Confirm Register pressure
5 Start Point e.g. 2 Current level =
level for "empty"
6 The tank is full (60...100 %)
7 Set Upper
Value
Confirm Register pressure
8 Full Scale e.g. 100 Current level =
level for "full"
9 Unit After Lin e.g. % Select level units
Result
• Level is displayed in "Measured Value"
Unit After LinearizationThe units for level, volumetric or weight are selected with the parameter "Unit After
Linearization". Selecting these units is only to help the operator. It has no effect on the
main measured value in parameter "Measured Value".
Example: 55 % is shown as 55 hl after selcting the unit "hl".
BA211Y46
Full
100 %
Empty
0%
Full
100 %
Empty
2%
BA211Y47
Cerabar S FF 6 Level Measurement