6.4 Damping
Output dampingThe damping influences the time it takes for the display in "Measured Value" to react to
a change in pressure.
# Parameter Entry Significance
1 Set Output
Damping
e.g. 30 Damping in
transducer block
increased to 30 s
Note!
Both the transducer block output and the analog input block can be damped. We
recommend that the damping be set in the transducer bloch during commissioning and
increased if necessary in the analog input block during normal operation. This prevents
the device switching to "Out of Service" when the parameter is edited.
6.5 Maximum pointer function
Maximum pointer
function
The maximum pointer function displays the maximum and minimum pressure and
temperature measured since the last pointer reset.
The units for pressure and temperature are selected with the parameter "Select Pressure
Unit" and "Select Temperature Unit" respectively. Please note that any change in the
pressure units affects all pressure entries.
0 τ 2τ 3τ
63 %
100 %
BA211Y41
pressure
signal
time
Parameter Signifiance
Min. Pressure
Minimum pressure, Reset via the option "reset" to the acting pressure value
using the parameter "Reset Min Pres Peak Hold"
Max. Pressure
Maximum pressure, Reset via the option "reset" to the acting pressure
value using the parameter "Reset Max Pres Peak Hold"
Min. Temperature
Minimum temperature, Reset via the option "reset" to the acting
temperature using the parameter "Reset min Peak Hold"
Max.Temperature
Maximum temperature, Reset via the option "reset" to the acting
temperature using the parameter "Reset max Peak Hold"
Note!
Cerabar S FF 6 Level Measurement
Endress+Hauser 43