7 Diagnosis and Trouble-Shooting
7.1 Diagnosis of errors and warnings
ErrorsWhen the Cerabar S detects an error:
•
An error code is transmitted along with the measured value.
•
If the display is present, the error code is displayed and flashes.
•
The current error code is displayed in parameter "Diagnostic Code", the last error
code in parameter "Last Diagnostic Code".
WarningsWhen the Cerabar S detects a warning:
•
An error code is transmitted along with the measured value: the Cerabar S
continues measuring.
•
The current error code is displayed in parameter "Diagnostic Code", the last error
code in parameter "Last Diagnostic Code".
Error codes in
"Diagnostic Code" and
"Last Diagnostic Code"
If several errors occur simultaneously, then they are displayed in sequence
corresponding to the priority of the error.
Code
Type Source and remedy
E 101 Error Electronic instrument error
– Remedy by Endress+Hauser Service
E 102 Warning Electronic instrument error with the maximum counter function
– Carry out reset (Code 5140), recalibrate the instrument
E 103 Error Initialising in progress
– Wait until the procedure is completed
E 104 Warning Sensor calibration
– Recalibrate sensor
E 110 Error Check sum error
– Carry out reset (Code 5140), the error remains
– Remedy by Endress+Hauser Service
E 111,
E 112,
E 113,
E 114
Error Electronic instrument error
– Remedy by Endress+Hauser Service
E 115 Error Sensor overpressure
– Remains until overpressure is no longer present
E 120 Error Sensor underpressure
– Remains until underpressure is no longer present
E 610 Error Calibration error, same pressure value for "Lower Range Value" and "Upper
Range Value"
– Check the calibration
E 620 Warning Measured value outside range