Ceraphant PTP31B, PTP33B Overview of the operating menu
Endress+Hauser 47
Switch output
1)
Level 1 Level 2 Level 3 Description Details
1 x PNP 2 x PNP 1 x PNP +
4 to 20 mA
FCU alarm current → 58
MIN In the event of an error: MIN (≤3.6 mA)
MAX In the event of an error: MAX (≥21 mA)
HLD Last current value (HOLD)
OFF Switch off the current output (only visible if switch output is "ON") → 58
NO
YES
ON Switch on the current output (only visible if switch output is "OFF") → 59
NO
YES
UNI Unit changeover → 59
BAR Unit bar
KPA Unit kPa (depends on the sensor measuring range))
MPA Unit MPa (depends on the sensor measuring range)
PSI Unit psi
HI Max value (maximum indicator) → 59
LO Min value (minimum indicator) → 60
ZRO Zero point configuration → 29
GTZ Zero point adoption → 30
TAU Damping → 61
DIS Display → 62
DVA PV Display measured value → 62
PV'/, Display the measured value as a percentage of the set span
SP Display set switch point
DRO Display measured value rotated by 180° → 62
NO
YES
DOF Display off → 62
NO
YES
ADM Administration
LCK Unlocking code → 24
COD Locking code → 24
DIAG Diagnostics
STA Current device status → 64
LST Last device status → 64
RVC Change counter → 64
SM1 Simulation output 1 → 64
OFF
OPN Switch output opened
CLS Switch output closed