Ceraphant PTP31B, PTP33B Description of device parameters
Endress+Hauser 53
13.2 Current output
STL value for 4 mA (LRV)
Navigation STL
Description Assignment of the pressure value which should correspond to the 4 mA value.
It is possible to invert the current output. To do so, assign the pressure upper range value
to the lower measuring current.
Prerequisite Electronic version with current output
Note Enter the value for 4 mA in the selected pressure unit anywhere within the measuring
range. The value can be entered in increments of 0.1 (increment depends on the
measuring range).
Selection No selection. The user is free to edit the values.
Factory setting 0.0 or as per order specifications
STU value for 20 mA (URV)
Navigation STU
Description Assignment of the pressure value which should correspond to the 20 mA value.
It is possible to invert the current output. To do so, assign the pressure lower range value
to the upper measuring current.
Prerequisite Electronic version with current output
Note Enter the value for 20 mA in the selected pressure unit anywhere within the measuring
range. The value can be entered in increments of 0.1 (increment depends on the
measuring range).
Selection No selection. The user is free to edit the values.
Factory setting Upper measuring limit or as per order specifications.