Ceraphant PTP31B, PTP33B Description of device parameters
Endress+Hauser 59
Selection NO (current output remains switched on)
YES (current output is switched off)
Factory setting NO
ON Switch on current output
Navigation EF → I → ON
Description Switches on the current output.
Prerequisite Is only displayed if the current output is switched off.
Selection NO (current output remains switched off)
YES (current output is switched on)
Factory setting NO
UNI unit changeover
Navigation EF → UNI
Description Select the pressure engineering unit. If a new pressure engineering unit is selected, all
pressure-specific parameters are converted and displayed with the new unit.
Value at switch-on Depends on order specifications.
Selection BAR (bar)
KPA (kPa) (depends on the sensor measuring range)
MPA (Mpa) (depends on the sensor measuring range)
PSI (psi)
Factory setting Depends on order specifications.
HI Max value (maximum indicator)
Navigation EF → HI
Description This parameter (also known as the maximum indicator) makes it possible to call up
retroactively the highest value ever measured for pressure.
A pressure that is present for at least 2.5 ms is logged to the maximum indicator.
The maximum indicators cannot be reset.
Factory setting Start value LRL, cannot be deleted afterwards