Description of device parameters Ceraphant PTP31B, PTP33B
64 Endress+Hauser
13.4 DIAG menu (diagnosis)
STA Current device status
Navigation DIAG → STA
Description Displays the current device status.
LST Last device status
Navigation DIAG → LST
Description Displays the last device status (error or warning) which has been rectified during
operation.
RVC Revision counter
Navigation DIAG → RVC
Description Counter that indicates the number of parameter changes.
SM1 Simulation output 1
Navigation DIAG → SM1
Description Switch output simulation.
If a simulation is active, a warning to this effect is displayed so that it is obvious to the user
that the device is in the simulation mode. A visual warning is indicated on the local display
(C485 - Simulation Active). The simulation must be ended actively via the menu. If the
device is disconnected from the power supply during the simulation and then power is
resupplied afterwards, the simulation mode is not resumed, and instead the device
continues operation in the measuring mode.
Selection • OFF
• OPN (switch output open)
• CLS (switch output closed)
SM2 Simulation output 2 (for devices with a 4 to 20 mA current output)
Navigation DIAG → SM2