Ceraphant PTP31B, PTP33B Description of device parameters
Endress+Hauser 65
Description Analog output simulation.
If a simulation is active, a warning to this effect is displayed so that it is obvious to the user
that the device is in the simulation mode. A visual warning is indicated on the local display
(C485 - Simulation Active). The simulation must be ended actively via the menu. If the
device is disconnected from the power supply during the simulation and then power is
resupplied afterwards, the simulation mode is not resumed, and instead the device
continues operation in the measuring mode.
Selection • OFF
• 3.5
• 4
• 8
• 12
• 16
• 20
• 21.95
SM2 Simulation output 2 (for devices with 2 switch outputs )
Navigation DIAG → SM2
Description Switch output simulation.
If a simulation is active, a warning to this effect is displayed so that it is obvious to the user
that the device is in the simulation mode. A visual warning is indicated on the local display
(C485 - Simulation Active). The simulation must be ended actively via the menu. If the
device is disconnected from the power supply during the simulation and then power is
resupplied afterwards, the simulation mode is not resumed, and instead the device
continues operation in the measuring mode.
Selection • OFF
• OPN (switch output open)
• CLS (switch output closed)