EasyManua.ls Logo

Endress+Hauser Ceraphant T PTC31 - Output Switching Characteristics

Endress+Hauser Ceraphant T PTC31
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning Ceraphant T PTC31, PTP31, PTP35
18 Endress+Hauser
OUT/OUT2 Output/output 2
Switching characteristic HYNO
1)
:
Hysteresis/NO contact
HYNC:
Hysteresis/NC contact
WINO:
Window/NO contact
WINC:
Window/NC contact
4...20 mA:
Analog output (only if
available)
1) Factory setting
Switch point value Switch point 0.5...100 %
URL
in increments of 0.1 % of
selected unit (min.
0.001 bar (0.015 psi))
Switch-back point value Switch-back point
0...99.5 % URL
in increments of 0.1 % of
selected unit (min.
0.001 bar (0.015 psi))
Switch point delay Delay time
0...99 s
in increments of 0.1 s
factory setting: 0.0
Switch-back point delay
Delay time
0...99 s
in increments of 0.1 s
factory setting: 0.0
!
Note!
Adjustment of measuring ranges with negative gauge pressure up to 4 bar (60 psi) in increments of min. 0.01 mbar
(0.15 psi).
Min. distance between SP and RSP: 0.5% URL

Related product manuals