Technical data CM14
36
Connection Description
134 Terminal for analog output 1, -
233 Terminal for analog output 2, +
234 Terminal for analog output 2, -
R11, R12, R13 Terminal for relay 1
R21, R22, R23 Terminal for relay 2
11.5.2 Supply voltage
Wide-range power supply 24 to 230 V AC/DC (-20 % / +10 %) 50/60Hz
The device does not have a power switch
The customer has to provide a protected circuit breaker close to the device.
The disconnector must be a switch or power-circuit breaker and must be identified as a
disconnector for the device.
11.5.3 Power consumption
Max. 13.8 VA / 6.6 W
11.6 Performance characteristics
11.6.1 Response time
Current outputs
t
90
= max. 500 ms for a jump from 0 to 20 mA
11.6.2 Reference temperature
25 °C (77 °F)
11.6.3 Maximum measured error of inputs
--> Documentation of the connected sensor
11.6.4 Resolution of current output
> 13 bit
11.6.5 Repeatability
--> Documentation of the connected sensor
11.7 Installation
11.7.1 Installation instructions
Mounting location
Panel, cutout 92 x 45 mm (3.62 x 1.77 in)
Max. panel thickness 26 mm (1 in)