Deltabar FMD71, FMD72 Description of device parameters
29
Options • In pressure
If this option is selected, specify two pressure/level value pairs. The level value is
displayed directly in the unit that you select via the "Unit Before Lin." parameter.
• In height
If this option is selected, specify two height/level value pairs. From the measured
pressure, the device first calculates the height using the density. This information is then
used to calculate the level in the "Unit Before Lin." selected using the two value pairs
specified.
Factory setting In pressure
Unit before lin. (025)
Navigation Expert → Measurement → Level → Level Before Lin. (025)
Write permission Operators/Service engineers/Expert
Description Select the unit for the measured value display for the level before linearization.
Example • Current measured value: 0.3 ft
• New output unit: m
• New measured value: 0.3 m
Options • %
• mm, cm, dm, m
• ft, in
• m
3
, in
3
• l, hl
• ft
3
• gal, Igal
• kg, t
• lb
Note The unit selected is only used to describe the measured value. This means that when
selecting a new output unit, the measured value is not converted.
Factory setting %
Height unit (026)
Navigation Expert → Measurement → Level → Height Unit (026)
Write permission Operators/Service engineers/Expert
Description Select the height unit. The measured pressure is converted to the selected height unit
using the "Adjust Density" parameter.
Prerequisite "Level Selection" = "In height"