Description of device parameters Deltabar FMD71, FMD72
64
Sim. Press. LP (285)
Navigation Expert → Diagnosis → Simulation → Sim. Press. LP (285)
Write permission Operators/Service engineers/Expert
Description Enter the simulation value. See also "Simulation Mode".
Prerequisite "Simulation Mode" = Pressure LP
Value at switch-on Current pressure measured value
Connect transm. (286)
Navigation Expert → System → Management → Connect transm. (286)
Write permission Service engineers/Expert
Description Determine the transmitter connection. After both sensor modules are replaced or if the
main electronics fail, the configuration has to be redefined using this parameter.
Options At sensor HP
At sensor LP
Factory setting At sensor HP
Sensor Changes (287)
Navigation Expert → Diagnosis → Sensor Changes (287)
Write permission No write permissions. Parameter is read only.
Description Displays the number of sensor module changes.
3rd disp. value (288)
Navigation Expert → System → Display → 3rd Disp. Value (288)
Write permission Operators/Service engineers/Expert
Description Specify the contents for the third value in the alternating display mode in measuring
mode.