Deltabar FMD71, FMD72 Diagnostics and troubleshooting
Endress+Hauser 67
Diagnostic event Cause Corrective measure
Code Description
F162 Sensor conn. Sensor module defective (master).
Electromagnetic effects outside the permitted
range. This message appears for a short time only.
Check the sensor module
cable
Replace sensor module
Contact Endress+Hauser
Service
F162 Sensor conn. HP
Sensor conn. LP
Electromagnetic effects outside the permitted
range. This message appears for a short time only.
Sensor module defective.
Check the sensor module
cable
Replace sensor module
Contact Endress+Hauser
Service
F163 Sensor conn. Cable connection between sensor modules HP and
LP interrupted.
Sensor module defective (slave).
Electromagnetic effects outside the permitted
range. This message appears for a short time only.
Restart device
Check the sensor module
cable
Contact Endress+Hauser
Service
F164 Sensor sync. The sensor modules cannot be synchronized with
each other.
Electromagnetic effects outside the permitted
range. This message appears for a short time only.
Sensor module(s) defective.
Restart device
Replace sensor module
Contact Endress+Hauser
Service
F165 Sensor
assignment
The assignment of the transmitter to sensor module
LP or HP is unknown (e.g. after changing the sensor
module). See also "Replacing sensor modules".
Connect transm. set.
Restart device
Contact Endress+Hauser
Service
F261 Electronics
module
Main electronics defective.
Fault in the main electronics.
Sensor module defective.
Restart device
Replace electronics
F282 Memory Main electronics defective.
Fault in the main electronics.
Replace electronics
Restart device
F283 Memory content Main electronics defective.
Electromagnetic effects are greater than
specifications in the technical data.
The supply voltage is disconnected when writing.
An error occurred when writing.
Perform a reset
Replace electronics
F411 Up-/Download The file is defective.
During the download, the data are not correctly
transmitted to the processor, e.g. because of open
cable connections, spikes (ripple) on the supply
voltage or electromagnetic effects.
Download again
Use another file
Perform a reset
F510 Linearization The linearization table is being edited. Conclude entries
Select "linear"
F511 Linearization The linearization table consists of less than 2 points. Table too small
Corr. table
Accept the table
F512 Linearization The linearization table is not monotonic increasing
or decreasing.
Tab. not monotonic
Corr. table
Accept the table
F841 Sensor range Overpressure or low pressure present.
Sensor module defective.
Check the pressure value
Contact Endress+Hauser
Service
F882 Input signal External measured value is not received or displays a
failure status.
Check the bus
Check source device
Check the setting
F945 Pressure limit LP The configured overpressure or underpressure
limit of sensor module LP is exceeded.
Sensor module LP defective.
Check the pressure value
Change pressure limit
value
Contact Endress+Hauser
Service