Deltabar FMD71, FMD72 Description of Device Parameters
Endress+Hauser 83
Note In the case of wet calibration, the level (vessel full) must actually be available. The
associated pressure is then automatically recorded by the device.
In the case of dry calibration, the level (vessel full) does not have to be available. For the
"In pressure" level selection, the associated pressure must be entered in the "Full pressure"
parameter. The associated height has to be entered in the "Full height" parameter for the
"In height" level selection.
Factory setting 100.0
Set LRV (013, 056, 166, 168)
Navigation
Setup → Set LRV (013, 056, 166, 168)
Setup → Extended setup → Current output → Set LRV (013, 056, 166, 168)
Write permission Operators/Service engineers/Expert
Description Set the pressure value, level or content for the lower current value (4 mA).
Factory setting 0.0 % in Level measuring mode
0.0 mbar/bar or in accordance with ordering information in Pressure measuring mode
Set URV (014, 057, 167, 169)
Navigation
Setup → Set URV (014, 057, 167, 169)
Setup → Extended setup → Current output → Set URV (014, 057, 167, 169)
Write permission Operators/Service engineers/Expert
Description Set the pressure value, level or content for the upper current value (20 mA).
Factory setting 100.0 % in Level measuring mode
URL Sensor or according to ordering information in Pressure measuring mode
Damping switch (164)
Navigation Setup → Damping switch (164)
Write permission No write permissions. Parameter is read only.
Description Displays the switch position of DIP switch 2 which is used to switch the damping of the
output signal on and off.