Deltabar FMD71, FMD72 Description of Device Parameters
Endress+Hauser 87
Options %
mm, cm, dm, m
ft, in
m
3
, in
3
l, hl
ft
3
gal, Igal
kg, t
lb
Note The unit selected is only used to describe the measured value. This means that when
selecting a new output unit, the measured value is not converted.
Factory setting %
Height unit (026)
Navigation Setup → Extended setup → Level → Height unit (026)
Write permission Operators/Service engineers/Expert
Description Select the height unit. The measured pressure is converted to the selected height unit
using the "Adjust Density" parameter.
Prerequisite "Level selection" = "In height"
Options mm
m
in
ft
Factory setting m
Calibration mode (027)
Navigation Setup → Extended setup → Level → Calibration mode (027)
Write permission Operators/Service engineers/Expert
Description Select the calibration mode.
Options Wet
Wet calibration takes place by filling and emptying the vessel. In the case of two
different levels, the level, volume, mass or percentage value entered is assigned to the
pressure measured at this point in time ("Empty calib." and "Full calib." parameters).
Dry
Dry calibration is a theoretical calibration. For this calibration, you specify two pressure-
level value pairs or height-level value pairs via the following parameters: "Empty calib.",
"Empty pressure", "Empty height", "Full calib.", "Full pressure", "Full height".