Description of Device Parameters Deltabar FMD71, FMD72
92 Endress+Hauser
Line number (039)
Navigation Setup → Extended setup → Linearization → Line number (039)
Write permission Operators/Service engineers/Expert
Description Enter the number of the current point in the table. The subsequent entries in "X-value" and
"Y-value" refer to this point.
Input range 1 to 32
X-value (040)/(123)/(193)
Navigation Setup → Extended setup → Linearization → X-value (040)/(123)/(193)
Write permission Operators/Service engineers/Expert
Description Enter the X-value (level before linearization) for the specific point in the table and confirm.
Note If "Lin. mode" = "Manual", the level value must be entered.
If "Lin. mode" = "Semiautomatic", the level value is displayed and has to be confirmed by
entering the paired Y-value.
Y-value (041)/(194)
Navigation Setup → Extended setup → Linearization → Y-value (041)/(194)
Write permission Operators/Service engineers/Expert
Description Enter the Y-value (value after linearization) for the specific point in the table. The unit is
determined by "Unit after lin.".
Note The linearization table must be monotonic (increasing or decreasing).
Edit table (042)
Navigation Setup → Extended setup → Linearization → Edit table (042)
Write permission Operators/Service engineers/Expert
Description Select the function for entering the table.