Description of Device Parameters Deltabar FMD71, FMD72
96 Endress+Hauser
Factory setting Cancel
Set LRV (013, 056, 166, 168)
Navigation
Setup → Set LRV (013, 056, 166, 168)
Setup → Extended setup → Current output → Set LRV (013, 056, 166, 168)
Write permission Operators/Service engineers/Expert
Description Set the pressure value, level or content for the lower current value (4 mA).
Factory setting • 0.0 % in Level measuring mode
• 0.0 mbar/bar or in accordance with ordering information in Pressure measuring mode
Get URV (016)
Navigation Setup → Extended setup → Current output → Get URV (016)
Write permission Operators/Service engineers/Expert
Description Setting upper range value. The pressure for the upper current value (20 mA) is present at
the device. Use the "Confirm" option to assign the applied pressure value to the upper
current value.
Prerequisite Pressure measuring mode
Options • Cancel
• Confirm
Factory setting Cancel
Set URV (014, 057, 167, 169)
Navigation
Setup → Set URV (014, 057, 167, 169)
Setup → Extended setup → Current output → Set URV (014, 057, 167, 169)
Write permission Operators/Service engineers/Expert
Description Set the pressure value, level or content for the upper current value (20 mA).
Factory setting • 100.0 % in Level measuring mode
• URL Sensor or according to ordering information in Pressure measuring mode