Deltabar M 4...20 mA HART Commissioning
Endress+Hauser 27
Max. pressure flow (010)
Entry
Enter maximum pressure of primry element.
→ See layout sheet of primary element. This pressure is assigned to the flow defined
in the "Max. flow" (009) parameter.
Damping switch (164)
Display
Displays the status of DIP switch 2 "damping τ", which is used to switch the
damping of the output signal on and off.
Damping value (017)
Entry/Display
Enter damping time (time constant τ). The damping affects the speed at which the
measured value reacts to changes in pressure.
!
Note!
The damping is only active if DIP switch 2 "damping τ" is in the ON position.
Flow (018)
Display
Displays the present flow value.
Pressure after damping (111)
Display
Displays the measured pressure after sensor trim, position adjustment and damping.
Parameter name Description