Commissioning Deltabar M 4...20 mA HART
32 Endress+Hauser
Description
1 Perform "position zero adjustment" → ä 24.
2 Select the "Level" measuring mode via the "Measuring
mode (005)" parameter (→ ä 23).
Menu path: Setup → Measuring mode
3 Select a pressure unit via the "Press eng. unit"
parameter (→ ä 24), here "mbar" for example.
Menu path: Setup → Press. eng. unit
4 Select the "In height" level mode via the "Level
selection" parameter.
Menu path: Setup → Extended setup → Level →
Level selection
5 Select a volume unit via the "Output unit" parameter,
here "l" for example.
Menu path: Setup → Extended setup → Level →
Output unit
6 Select a height unit via the "Height unit" parameter,
here "m" for example.
Menu path: Setup → Extended setup → Level →
Height unit
7 Select the "Wet" option via the "Calibration mode"
parameter.
Menu path: Setup → Extended setup → Level →
Calibration mode