Deltabar S
Endress+Hauser 15
FOUNDATION Fieldbus
Supported features Identification & Maintenance
Simple device identification via control system and nameplate
•Condensed status
1)
Automatic ident number adaptation and switchable to following ident
numbers
)
:
9700: Profile-specific transmitter identification number with the "Classic" or
"Condensed" status".
1504: Compatibility mode for the old Deltabar S generation (FMD230,
FMD630, FMD633, PMD230, PMD235).
1542: Identification number for the new Deltabar S generation (FMD76,
FMD77, FMD78, PMD70, PMD75).
Device locking: The device can be locked by hardware or software.
1) Only with Profile Version 3.02
Manufacturer ID 452B48 hex
Device type 1009 hex
Device Revision 6 - SW Version 03.00.zz
7 - SW Version 04.00.zz (FF-912)
DD Revision 3 (Device Revision 6)
•2 (Device Revision 7)
CFF Revision 4 (Device Revision 6)
•1 (Device Revision 7)
DD Files Information and files can be found:
www.endress.com
www.fieldbus.org
CFF Files
Device Tester Version (ITK
Version)
5.0 (Device Revision 6)
6.01 (Device Revision 7)
ITK Test Campaign Number IT054700 (Device Revision 6)
IT085400 (Device Revision 7)
Link Master (LAS) capable yes
Link Master / Basic Device
selectable
Yes, default is Basic Device
Node Address Default: 247 (F7 hex)
Supported features Field Diagnostics Profile
1)
Following methods are supported:
•Restart
Configure error as warning or alarm
•HistoROM
Peakhold
•AlarmInfo
•SensorTrimm
1) Only with FF912
Number of VCRs 44 (Device Revision 6)
24 (Device Revision 7)
Number of Link Objects in VFD 50