Deltabar S
16 Endress+Hauser
Virtual communication references (VCRs)
Link settings
Transducer Blocks
Device Revision 6 Device Revision 7
Permanent Entries 44 1
Client VCRs 0 0
Server VCRs 5 10
Source VCRs 8 43
Sink VCRs 0 0
Subscriber VCRs 12 43
Publisher VCRs 19 43
Device Revision 6 Device Revision 7
Slot time 4 4
Min. inter PDU delay 12 10
Max. response delay 10 10
Block Content Output values
TRD1 Block Contains all parameters related to the measurement Pressure, flow or level (channel 1)
Process temperature (channel 2)
Service Block Contains service information Pressure after damping (channel 3)
Pressure peakhold indicator (channel 4)
Counter for max. pressure transgressions
(channel 5)
Dp Flow Block Contains flow and totalizer parameter Totalizer 1 (channel 6)
Diagnostic Block Contains diagnostic information Error code via DI channels (channel 0 to 16)
Display Block Contains parameters to configure the onsite display No output values