Devices with 7/8" plug
PIN assignment for 7/8" connector
External thread: 7/8 - 16 UNC
• Material: 316L (1.4401)
• Degree of protection: IP68
Cable gland
Terminals
For wire cross-sections of 0.5 to 2.5 mm² (20 to 14 AWG)
Measuring a 4 to 20 mA test signal
A 4 to 20 mA test signal may be measured via the positive and test terminal without interrupting the
measurement. The minimum supply voltage of the device can be reduced by simply changing the position of
the jumper. As a result, operation is also possible with lower voltage sources. Observe the position of the jumper
in accordance with the following table.
A0011176
PIN Meaning
1 Signal –
2 Signal +
3Not assigned
4Shield
Approval Type Clamping area
Standard, II1/2G Exia, IS Plastic M20x1.5 5 to 10 mm (0.2 to 0.39 in)
ATEX II1/2D, II1/3D,
II1/2GD Exia, II1GD Exia
II3G Ex nA
Metal M20x1.5 (Ex e) 7 to 10.5 mm (0.28 to 0.41 in)
Jumper position for test signal Description
– Measuring 4 to 20 mA test signal via the plus and test terminal:
possible. (Thus, the output current can be measured without
interruption via the diode.)
– Delivery status
– Minimum supply voltage: 11.5 V DC
– Measuring 4 to 20 mA test signal via the plus and test terminal:
not possible.
– Minimum supply voltage: 10.5 V DC