Commissioning Deltabar S PROFIBUS PA
24 Endress+Hauser
5.2 Differential pressure measurement
•FMD78: the device is ready for calibration immediately.
•PMD70 and PMD75: before calibrating the device, the impulse piping must be cleaned and
filled with fluid. See the following table.
5.2.1 Quick Setup menu for Pressure measuring mode – on-site display
!
Note!
See also Page 15, Section 4.2.3 "Function of the operating elements" and Page 16, 4.3 "On-site
operation via on-site display".
P01-xMD7xxxx-19-xx-xx-xx-077
Abb. 10: Quick Setup menu for Pressure measuring mode
GROUPSELECTION
MEASURING MODE
LANGUAGE
OPERATING MENU
POS. ZEROADJUST
DAMPINGVALUE
Flow
Pressure
Level
MEASURED VALUE
QUICKSETUP
On-site operation
Measured value display
On-site display: Switch from the measured value display to GROUP SELECTION with F.
GROUP SELECTION
Select MEASURING MODE.
MEASURING MODE
Select "Pressure" option.
GROUP SELECTION
Select QUICK SETUP menu.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in the measured value. You correct the MEASURED VALUE via
the POS. ZERO ADJUST parameter with the "Confirm" option, i. e. you assign the value 0.0 to the pressure present.
DAMPING VALUE
Enter damping time (time constant τ). The damping affects the speed at which all subsequent elements, such as the
on-site display, measured value and OUT value of the Analog Input Block react to a change in the pressure.