Deltabar S PROFIBUS PA Commissioning
Endress+Hauser 27
5.3.1 Quick Setup menu for Level measuring mode – on-site display
!
Note!
•Some parameters are only displayed if other parameters are appropriately configured (see the
following table).
•The following parameters are set to the following values in the factory:
–LEVEL SELETION: Level Easy Pressure
–CALIBRATION MODE: Wet
–OUTPUT UNIT or LIN. MEASURAND: %
–EMPTY CALIB.: 0.0
–FULL CALIB.: 100.0
For parameter description see CD-ROM, Operating Instructions BA00296P.
•The quick setup is suitable for simple and quick commissioning. If you wish to make more
complex settings, e.g. change the unit from "%" to "m", you will have to calibrate using the
BASIC SETTINGS group.
•See also Page 15, Section 4.2.3 "Function of the operating elements" and Page 16, 4.3 "On-site
operation via on-site display".
P01-xMD7xxxx-19-xx-xx-xx-075
Abb. 11: Quick Setup menu for Level measuring mode
1)
1)
1) LEVELSELECTION "Level Easy Pressure"
and CALIBRATION MODE "Wet"
LEVELSELECTION = "Level Standard",
LEVEL MODE = "Linear" and
CALIBRATION MODE ="Wet"
POS. ZEROADJUST
EMPTY CALIB.
FULL CALIB.
DAMPINGVALUE
Flow
Pressure
Level
MEASURED VALUE
QUICKSETUPLANGUAGE
OPERATING MENUMEASURING MODE
GROUPSELECTION
LEVELSELECTION
On-site operation
Measured value display
On-site display: Switch from the measured value display to GROUP SELECTION with F.
GROUP SELECTION
Select MEASURING MODE.