10 Operating Matrix
10.1 Matrix operation
H0 H1 H2 H3 H4 H5 H6 H7 H8 H9
Basic
calibration
V0
Measured
value
customer unit
"Empty"
calibration
m/ft
[20] (24,26)
"Full"
vcalibration
m/ft
[20] (24,26)
Application
0: Tank 7 m
1: Tank 1.5 m
2: Tank 7 m,
εr<10
3: Tank 20 m
4: SW 7 m
5: SW 1.5 m
6: SW 20 m
[0] (24,26)
Output damping
0…255 s
[5] (31)
Value for
4mA
[0] (31)
Value for
20 mA
[100] (31)
Safety alarm
MIN.:0
MAX.:1
HOLD:2
[1] (31)
Measured
diatance
m/ft
Level before
lineariastion
m/ft
V1
Lineari-
sation
V2
Linearisation
level m/ft:0
activate tab.:1
man. entry:2
semi-auto:3
clear:4
linear:5
[5] (28)
Table No.
(28)
Input
level
m/ft
(28)
Input
volume
customer unit
(28)
Max. volume
customer unit
[100] (28)
Extended
calibration
V3
False echo
suppression
factory.:0
customer.:1
up to echo:2
incl. echo:3
to distance.:4
[0] (23, 25)
Suppression
distance
m/ft
(23, 25)
Echo quality
dB
(40)
Microfactor
[1.00] (25)
First echo
factor
MIN.:0
MITTEL:1
MAX.:2
[2] (39)
Window
suppression
[Antenna-
tip] (41)
Offset*
m/ft
*
V4…V7
Operating
mode
V8
Current output
min 4 mA:
off:0
on:1
[1] (31)
Length unit
m:0
ft:1
[0/1] (24,26)
Delay on lost
echo
0255 s
[30] (32)
In safety
distance
warning:0
alarm:1
self-holding:2
clear 2:3
[0] (32)
Plausibility
off: 0
on: 1
[0] (42)
Service/
Simulation
V9
Diagnosis
code
(36)
Last diagnosis
code
(36)
Communication
and software
version
HART device
address
Reset to factory
settings
[333] (44)
Simulation
off:0
level:1
volume:2
current:3
[0] (43)
Simulated
value
Output current
mA
Locking
<> 333
lock
=333
unlock
Communi-
cationVA
Tag No. Units, measured
value
Display
Factory setting Page
[00] (00)
* Not required for rod antenna
Chapter 10 Operating Matrix Micropilot FMR 231