Gammapilot FMG50
Endress+Hauser 15
Density, concentration, interface and mass flow measurements
• 5000 cnt/s for
137
Cs
• 5000 cnt/s for
60
Co
Density and concentration measurements
• Depends on the application; for more information contact Endress+Hauser Service or the "Gamma
Project Team" (gamma@endress.com)
• Applicator
https://www.de.endress.com/de/onlinetools/life-cycle-management/Planung-Engineering-
Rueckverfolgbarkeit/Applicator-Produktauswahl-Produktauslegung
An application can deliver satisfactory measurement results even if the pulse rate is higher or
lower than the values specified here. For more information contact Endress+Hauser Service or
the "Gamma Project Team" (gamma@endress.com)
Measuring range Level measurement
In the case of level measurement, the measuring range typically depends on the height of the vessel.
To cover the entire measuring range, a scintillator is used that is longer than the measuring range.
Several Gammapilot FMG50 units can be used for measuring ranges >3 m (9.84 ft).
A0037672
1 Gammapilot FMG50
Max. point level detection
In the case of point level detection, the measuring range is essentially at one specific point. It is
determined by the thickness of the scintillator (42 mm (1.65 in)).
A0036644
1 Gammapilot FMG50
Min. Point level detection
In the case of point level detection, the measuring range is essentially at one specific point. It is
determined by the thickness of the scintillator (42 mm (1.65 in)).