Gammapilot FMG50
24 Endress+Hauser
4
5
C
3
2
2
2
16
B
A
11
X8
D
.
.
-
1
+
-
1
+
-
1
+
-
X4
A0018092
A Wiring with RTA421 switching unit
B Wiring with control system (pay attention to the explosion protection regulations)
C Wiring with RMA42 switching unit
D When installing in hazardous areas, please observe the corresponding Safety Instructions
1 Gammapilot FMG50
2 4 to 20 mA
3 RTA421
4 PLC (pay attention to the explosion protection regulations)
5 RMA42
Ex applications in conjunction with RMA42
Observe the following Safety Instructions:
ATEX II (1) G [Ex ia] IIC, ATEX II (1) D [Ex ia] IIIC for RMA42
XA00095R
SIL applications for Gammapilot in connection with RMA42
The Gammapilot FMG50 meets the requirements of SIL2/3 as per IEC 61508, see:
FY01007F
The RMA42 meets SIL2 as per IEC 61508:2010 (Edition 2.0), see the Functional Safety Manual:
SD00025R
Post-connection check
After wiring the device, carry out the following checks:
Is the potential matching line connected?
Is the terminal assignment correct?
Are the cable glands and dummy plugs screwed tight?
Are the fieldbus connectors properly secured?
Are the covers screwed down correctly?