A Wiring with RTA421 switching unit
B Wiring with control system (pay attention to the explosion protection regulations)
C Wiring with RMA42 switching unit
D When installing in hazardous areas, please observe the corresponding Safety Instructions
1 Gammapilot FMG50
2 4 to 20 mA
3 RTA421
4 PLC (pay attention to the explosion protection regulations)
5 RMA42
Ex applications in conjunction with RMA42
Observe the following Safety Instructions:
ATEX II (1) G [Ex ia] IIC, ATEX II (1) D [Ex ia] IIIC for RMA42
XA00095R
SIL applications for Gammapilot in connection with RMA42
The Gammapilot FMG50 meets the requirements of SIL2/3 as per IEC 61508, see:
FY01007F
The RMA42 meets SIL2 as per IEC 61508:2010 (Edition 2.0), see the Functional Safety Manual:
SD00025R
Post-connection check
After wiring the device, carry out the following checks:
 Is the potential matching line connected?
 Is the terminal assignment correct?
 Are the cable glands and dummy plugs screwed tight?
 Are the fieldbus connectors properly secured?
 Are the covers screwed down correctly?