Gammapilot FMG50 HART Commissioning
Endress+Hauser 23
2. Start SmartBlue.
3. Select device from livelist displayed.
4. Enter the login data:
User name: admin
Password: serial number of the device or ID number of the Bluetooth display
An available Bluetooth connection is indicated by a flashing Bluetooth symbol.
5. Tap the icons for more information.
For commissioning, see the "Commissioning Wizard" section
Change the password after logging in for the first time!
Bluetooth is not available in all markets.
Please pay attention to the radio approvals listed in document SD02402F or contact the
Endress+Hauser sales organization.
7.3.3 Operation via local display
Operation via keys is only active if a display is not attached
The device can also be operated on site using the keys. If operation is locked using the DIP
switches on site, parameter entry via communication is not possible.
1
2
Alarm
on
off
MaxSW
Zero/I
Span/II
Display
34
A0039285
1 Operating key for empty calibration (function I)
2 Operating key for full calibration (function II)
3 DIP switch for alarm current (SW-defined/Min. alarm)
4 DIP switch for locking and unlocking the device
Empty calibration: Press and hold the operating key for empty calibration (I) > 3 s
Full calibration: Press and hold the operating key for full calibration (II) > 3 s
Background calibration: Simultaneously press and hold the operating key for empty
calibration (I) and operating key for full calibration (II) > 3 s
Reset to factory defaults: Simultaneously press and hold the operating key for empty
calibration (I) and full calibration (II) > 12 s. The LED starts flashing. When the flashing
stops, the device is reset to the factory default settings.