Gammapilot FMG50 Electrical connection
Endress+Hauser 37
A0040224
10 Connection diagram: for two FMG50 units connected to one RMA42
1 RMA42
Sample settings for cascade mode
‣
FMG50 settings:
All FMG50 units used in cascade must be adjusted individually. For example via the
"Commissioning" Wizard in the "Level" operating mode.
The following example refers to a cascade measurement with 2 detectors:
Detector 1: 800 mm measuring range
Detector 2: 400 mm measuring range
1. Settings for RMA42 (analog input 1):
Signal type: current
Range: 4 to 20 mA
Lower range value: 0 mm
Upper range value: 800 mm
Offset where applicable
2. Settings for RMA42 (analog input 2):
Signal type: current
Range: 4 to 20 mA
Lower range value: 0 mm
Upper range value: 400 mm
Offset where applicable
3. Calculated value 1:
Calculation: sum total
Unit: mm
Bar graph 0: 0 m
Bar graph 100: 1.2 m
Offset where applicable
4. Analog output:
Assignment: calculated value 1
Signal type: 4 to 20 mA
Lower range value: 0 m
Upper range value: 1.2 m
Only the current output of the RMA42 supplies the level measured value of the
overall system. No HART values available for the entire cascade.