Gammapilot FMG50 Electrical connection
Endress+Hauser 39
2. Configure the HART variable PV (Primary Value) as "Level"
PV (level) is not relevant for the calculation
3. Configure the HART variable SV (Secondary Value) as "Pulse rate"
SV (pulse rate) is relevant for the calculation
4. Connect HART channels with the RSG45
5. Edit the linearization table in the RSG45
Value pairs (max. 32): pulse rate of cascade (total pulse rate) to cascaded level
(total level)
The pulse rates (cnt/s) of all the FMG50 units in the cascade are added in the RSG45
and then linearized
Example of a linearization table
Linearization point Total pulse rate
cnt/s
Total level
%
21 0 100
20 39 95
19 82 90
18 129 85
17 178 80
16 230 75
15 283 70
14 338 65
13 394 60
12 451 55
11 507 50
10 562 45
9 614 40
8 671 35
7 728 30
6 784 25
5 839 20
4 892 15
3 941 10
2 981 5
1 1013 0
Determine value pairs during commissioning
5.11.4 Ex applications in conjunction with RMA42
Observe the following Safety Instructions:
ATEX II (1) G [Ex ia] IIC, ATEX II (1) D [Ex ia] IIIC for RMA42
XA00095R