Commissioning Gammapilot FMG50
58 Endress+Hauser
A0042194
The normalized pulse rate and the customer value can be entered directly in table form in
this module.
The linearization table must be activated by selecting "Activate table" -> "Enable"
Semi-automatic
A0042195
During semi-automatic linearization, the device measures the pulse rate for every
linearization point. The associated level value is entered manually. In contrast to the
normalized pulse rate, the measured pulse rate is directly applied to the linearization table
in the semi-automatic mode.
The linearization table consists of up to 32 "measured pulse rate : level" value pairs.
Linearization table conditions
• The table can consist of up to 32 "level - linearized value" pairs.
• The table must decrease monotonically
• The first value in the table must correspond to the minimum level
• The last value in the table must correspond to the maximum level
The table values can be sorted as monotonically decreasing using the "Table mode -> Sort
table" function.